The maximum load power supported by the DC system is the minimum value between the output power of the power module and the output power of the lithium battery module. For example, the parallel output power of 2 power supplies is 5.7kW, the output power of 1 50Ah lithium battery is 3kW, and the maximum load power of the system is 3kW.
When the power supply is paralleled, under the condition of high temperature (ambient temperature > 50°C + solar radiation), the derating factor is 0.95, and the maximum output power of the power supply is 5.7kW (the maximum output of a single power supply is 2.85kW). In other working scenarios, the power is derated according to the module adaptively.
In the scenario of connecting to a lithium battery, the system works in 57V regulated mode, and if you need to customize the output voltage, you need to evaluate and implement it according to the actual load situation
Model Number |
DPU60D-N06A1 |
Output Type |
Multiple |
Input Voltage |
220V |
Output Voltage |
48V |
Output Frequency |
60Hz, 50Hz |
Output Current |
60A |
type |
AC-DC |
Input |
220V Single-phase three-wire input |
Input frequency |
45-65 Hz |
Power factor |
≥ 0.95 |
Output voltage range |
42-58 V DC |
Solutions
We offer all-encompassing solutions tailored for telecommunication companies, both within and beyond China's borders. Our services span from in-depth site surveys to crafting bespoke, professional plans that align precisely with customer demands. Alongside, we provide unwavering technical support and comprehensive maintenance services. With a highly skilled team and a global network of reliable partners, we stand out as a one-stop solution provider.