Eltek Flatpack S 24V 2U height with 3 rectifiers Flatpack S 24/1000HE FlatpackS 24/1800HE (MFGS0302.001 MFGS0302.002)
This small power dense system is purely based on pluggable breakers and rectifiers and can easily be configured to fit your required application, even in field. The combination of Flatpack S HE rectifiers and Smartpack S controller ensures safe, reliable and environmental friendly operation.
With its shallow depth and flexibility the Flatpack S 2U 2-pole system fits most cabinets and is thereby excellent as replacement unit.
Parameters :
|
|||||||
MODEL FPS 2U/3R 2-POLE 24V FPS 2U/3R 2-POLE 24V LVBD | |||||||
Part number | MFGS0302.001 MFGS0302.002 | ||||||
INPUT DATA | |||||||
Voltage (nominal) |
1) 185VAC/DC – 305VAC / 300VDC |
||||||
Mains configuration (individual feed) | 230VAC, 3 x 1 phase or 3 phase (∆) 230/400VAC, 3 phase (Y) | ||||||
Maximum current | 5,9Arms individual feed / 17,7Arms single feed | ||||||
Mains connection | 4mm2 terminal blocks, rear connection | ||||||
Frequency | 45 – 66Hz | ||||||
OUTPUT DATA | |||||||
Nominal Voltage | 24VDC | ||||||
Maximum current (total) | 125ADC | ||||||
Maximum current distribution (total) | 100ADC | ||||||
BATTERY DISTRIBUTION | |||||||
Breaker, 2-pole pluggable D-frame | 1 x 100Amax | ||||||
LVBD | N/A | Default | |||||
Connection (rear) | M6 studs (25mm2) | ||||||
Battery fuse alarm | Auxiliary switch | ||||||
LOAD DISTRIBUTION | |||||||
Breakers, 2-pole pluggable B-frame | 10 x 20Amax | ||||||
Connection (rear) | Screw terminals (10mm2) | ||||||
Load fuse alarm | Auxiliary switch | ||||||
BULK OUTPUT | |||||||
Protection Unfused | |||||||
Connection (rear) M6 Studs (25mm2) | |||||||
CONTROL & MONITORING | |||||||
Smartpack S | 6 x Input / Output and Ethernet2) | ||||||
OTHER SPECIFICATIONS | |||||||
Temperature | Operating: -40 to + 65°C full / +85°C derated Storage: -40 to + 85°C | ||||||
Coding | Coding to prevent insertion of incorrect power module | ||||||
Dimensions (W x H x D) | 482,5 x 89 x 250mm | ||||||
Mounting | 19” Flush mount | ||||||
Cooling | 30mm space in front and back required for air flow | ||||||
Weight (without rectifiers and breakers) | Approx. 7kg | ||||||
DESIGN STANDARDS | |||||||
Electrical safety | UL 60950-1, EN 60950-1, CSA C22.2 | ||||||
EMC |
ETSI EN 300 386 V.1.6.1 EN 61000-6-1 / -2 / -3 / -4 FCC Part 15 Subpart 109 |
||||||
Environment |
ETSI 300 019-2 -1 Class 1.2 ETSI 300 019-2 -1 Class 2.3 ETSI 300 019-2 -1 Class 3.2 |
||||||
1) See Flatpack S datasheet for details 2) See Smartpack S datasheet for details |
Related Products:
Solutions
For telecommunication companies operating in China and internationally, we provide a complete solution framework. Starting with an in-depth site survey, we then craft professional plans that are in line with customer requests. Our technical support and maintenance services are designed to offer peace of mind. With a competent team and a global network of trusted partners, we offer a differentiated and reliable service.