Specifications
Brand: Eltek
Part Number: 242100.510
Product Name: Telecom Controller
Model Name: Smartpack Touch
Serial Ports: RS-232 & RS-485
USB: 2 X USB Type A Host
SNMP: V1, V2c, V3 W/ GET, SET & TRAPs – Eltek Enterprise MIB Branch 10
Power Consumption: Max 5.4W, Typical 2.4W
Ethernet Ports: 2 X 10/100 BASE-T, Wi-Fi Support W/ USB Dogle
Weight: 2 Kg
Package: Cartons
Highlight:

242100.510 Telecom Monitoring Module Smartpack2 Touch

,

DC power systems 242100.510

,

242100.510 Telecom Monitoring Module

Basic Infomation
Place of Origin: CN
Brand Name: Eltek
Certification: CE,UL
Model Number: Smartpack Touch
Payment & Shipping Terms
Packaging Details: cartons
Delivery Time: 1-2 weeks
Payment Terms: L/C,T/T
Supply Ability: 1000 pieces / month
Product Description

Eltek Telecom Monitoring Module Smartpack2 Touch for DC power systems(Part No.:242100.510 . 242100.501 , 242100.601 )DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 0
 
Eltek Telecom Monitoring Module Smartpack2 Touch for DC power systems(Part No.:242100.510 . 242100.501 , 242100.601 )

The Smartpack2 Touch controllers are powerful modules used as master controllers in the distributed control system of Smartpack2-based power supply systems.

It is equipped with a graphical display with capacitive touch interface to show and control functions of system.


SP2Touch is the interface for system information, and communicates with SP2 Basic, SP2 Basic Industrial and other nodes and power modules via CAN.


Connecting to the Ethernet port allows easy access to the SP2Touch embedded web pages. The Smartpack2 Touch controller have the same shape as the older Smartpack2 Master (2U high and 160mm wide) and can easy replace it in the power system’s front panel or door.


DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 1


Key Features :

  •  Touch Screen 4.4’’ running the web interface
  •  LEDs for local visual alarming (Major, Minor, Power ON)
  •  Ethernet port at the back for permanent connection for monitoring and control
  •  Ethernet port at the front - a 'Craft port' with limited functionality and fixed ip-adr.
  •  USB port in the front and back for flash drives, Wi-Fi Adapter Dongle etc.
  •  RS-232 and RS-485- for communication w/3rd party equipment
  •  SNMP protocol with TRAP, SET and GET on Ethernet.
  •  Email of TRAP alarms
  •  Comprehensive logging
  •  Automatic battery monitoring and test
  •  Battery lifetime indication
  •  Battery used and remaining capacity (Ah or %) monitoring
  •  User defined alarm grouping (Boolean logic for grouped alarms)
  •  Comprehensive generator/hybrid/DC solar system control and monitoring features

DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 2

DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 3


Parameters :







SPECIFICATIONS


TOUCH

Part number 242100.510

System Compability 12Vdc to 380Vdc, Positive / Negative / Floating Distribution. Panel Mount

Power consumption Max 5.4W, Typical 2.4W

Display Graphical 4,4 inches LCD display - Capacitive touch interface - 480 x RGB x 272 resolution

Ethernet Ports 2 x 10/100 BASE-T, Wi-Fi support w/ USB dogle

Serial Ports RS-232 & RS-485

USB 2 x USB Type A Host

Removable media uSD card, USB Flash Drive support

SNMP v1, v2c, v3 w/ GET, SET & TRAPs – Eltek Enterprise MIB Branch 10

Web Interface Responsive HTML5, java script, encrypted w/TLS

Other network SMTP Client, NTP Client, FTP/FTPS file transfer, MODBUS TCP

Buzzer 75dB at 1m

IP Grade 22

Dimensions (WxHxD) 174 x 78 x 41 mm (Cut-out: 153 x 68 mm)

BASIC

Part number 242100.501

Operating temperature -20 to +70˚C (-4 to 158˚F)

Storage temperature -40 to +85˚C (-40 to 185˚F)

Input voltage 20-172 VDC (20 -75 VDC***) Shutdown: < 18 VDC

Power consumption Max 1.5A Max 4.5A (3x LVD max loaded)

Contactor outputs 3 x LVD control outputs

Configurable inputs 3x NO/NC/Temperature: NTC probe

System connections:

• Voltage sense

• Current sense

• Battery fuse*

• Load fuse*


24V, 48V, 60V & 110V** systems 0-20mV and 0-60mV range shunts Battery fuse sense, Open/Closed

Load fuse sense, Open/Closed, Pull- Up/Down, Diode Matrix



Ground fault Simple bridge circuit detection

Max basic nodes 8 units on a single CAN-bus

Dimensions (WxHxD) 155 x 35 x 80 mm / 6.4 x 1.4 x 3.3”

BASIC INDUSTRIAL

Part number 242100.601

Operating temperature -20 to +70˚C (-4 to 158˚F)

Storage temperature -40 to +85˚C (-40 to 185˚F)

Power consumption Max 1.6A

Electric isolation 7 different isolated sections

Customer connections:

• Configurable Inputs

3x, “digital”, temperature / voltage /current measurements.

- NO/NC, Pull Up/Dn, Diode Matrix: -10V> +10V (2mV full range)

- Current measurements: 4-20mA (ext. sense resistor 100-500Ω)

- Temperature measurements: NTC probe


Specifications are subject to change without prior notice



DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 4
 
 

DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 5

DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 6


DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 7DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 8DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 9
 
DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 10
DC Power Systems 242100.510 Telecom Monitoring Module Smartpack2 Touch 11
Solutions
We provide a complete solutions including site survey, propose professional plan according to customer’s request ,technical support, and maintenance service for Telecommunication Companies in and out of China. We have a competent team and a network of trusted Partners around the world.
 
FAQ :
1. How do you control the quality?
A:All products before the shipment are simulated usage scenarios, load and full load and current sharing test to ensure the quality of the product.
 
2. What is your minimum order quantity?
A:There is no minimum order quantity, and one can also be done. The only difference is the price and schedule.
 
3. Can you introduce your company?
A:I am very honored. I will send you the company’s introduction document later to give you a more comprehensive and direct introduction to our company’s information.
 
4. What are the advantages of your company?
A:Adequate inventory, and supply guarantee for the subsequent renewal of supply, flexible provided according to different to different needs of customers, providing different solutions.
 
5. Can i send samples?Report it to me along with the price?
A:You can send samples, the samples are subject to large pride, and the freight needs to be borne by you.
 
6. How do your company deal with the problem on quality?
A:Our company has been doing this industry for almost 10 years. It has already had a certain reputation. We will carefully analyze it. If it is indeed our quality problem, you can rest assured that it will do things according to the contract agreement and will never let you have any after the worries, our service team will be happy to serve you.
 
7 What about the quality ?
A:100% original with new package. we will test each item before posted to make sure each item with good quality.
 
8 How many months for guarantee ?
A: 1 year quality guarantee
 
9 How to deal with any inferior -quality goods ?
A: Goods can be post by with our charge of post fee for any bad quality products within guarantee time.
 
 

Recommended Products
Get in touch with us
Contact Person : Lee
Tel : 13011182266
Fax : 86-010-80303109
Characters Remaining(20/3000)